Plan ahead: no plan review Dec. 7, no inspections Dec. 11 – Our Plan Review staff will be training on Dec. 7 and unable to return emails or phone calls until the following day. There will be no inspections on Dec. 11 as Inspectors will be in training all day. As usual, our program will be off Nov. 10 for Veteran's Day, and Nov. 23 and 24 for Thanksgiving.
Permit extension policy – Beginning Jan. 1, 2024, plumbing & gas permits will only be granted (1) 18 month extension. An additional 90 day ‘Final-Only’ permit extension is available if rough-in inspection has already been performed. During the height of the COVID pandemic, our permit extension policy was amended to allow up to (2) 18-month extensions. That modified policy was originally set to expire on Dec. 31, 2022, but was extended to Dec. 31, 2023.
Please give us your feedback! – King County Plumbing & Gas is planning to refine some existing services and develop new ones with a goal of improving overall customer satisfaction. We would appreciate if you can set aside a couple of minutes to respond to this short, anonymous customer satisfaction survey.
New design guidance revision posted – We developed a new and reformatted version of our general Commercial Plumbing Design Guidance document. Our first revision (dated 10/13/2023) allows for a smaller AHJ Approval stamp box. All revisions will have the revision date noted in red text in the left margin of the document as shown below:
 Introducing guidance references in plan review correction comments – When our commercial plumbing design guidance document was updated, we made sure to include an alpha-numeric designation for each section and note. This allows us to reference a specific part of the guidance document when writing correction comments. In the coming weeks and months, you will begin to see these references being introduced into plan review summaries. For example, if a Narrative of Scope is incomplete, instead of issuing a multi-sentence correction note, the correction may simply state: “Provide complete Narrative of Scope per Guidance item 2E and note 2i.” This will help ensure our correction comments are clear and consistent between different projects and different reviewers.
Plan Review Timelines – The plan review cycle time for most projects (between application acceptance and first round comments) is currently around 6-8 weeks. Some large or complex projects may take additional time. Smaller projects typically take less time.
By Dave Price, Assistant Chief Plumbing Inspector, Public Health - Seattle & King County
Many years ago, when the price of copper began to fluctuate wildly and often exceeded the cost of stainless steel, we started to see stainless steel being proposed for use as a material in domestic water piping systems. When stainless steel was officially added to UPC Table 6-4 in the 2009 cycle, there were still lingering questions about the fitting requirements for these systems. Up until the 2021 UPC, there were no Referenced Standards for stainless steel water distribution fittings listed within Table 6-4.
Some local contractors and fabrication shops realized they could fabricate their own stainless fittings at a lower cost than what could be purchased off-the-shelf. Noticing this trend, Public Health - Seattle & King County asked IAPMO directly if there were any applicable Standards that we could reference to inform the industry of specific manufacturing requirements for these types of fittings. All domestic water fittings regardless of material already had to meet the requirements of NSF 61 as noted in UPC Section 604.1. However, there were no manufacturing standards being applied to the actual fabrication of stainless steel fittings.
After discussions with the IAPMO Answers & Analysis committee, investigation of various fitting standards, and an in-depth reading of published NSF documentation, it was determined that these locally fabricated fittings and assemblies needed to be listed to both NSF 61 and IAPMO PS 53 (in the case of grooved fittings) in order to be considered UPC compliant. A publication issued by NSF clarified that a fitting constructed entirely of an Approved material (listed in Annex C of the NSF 61 Standard) could not be represented as certified to NSF 61 as had been the popular assumption at the time. That meant each type of fabricated fitting would need to be independently tested by NSF in order to be considered certified. Further, the IAPMO A&A Committee confirmed that when a thread-o-let, weld-o-let, flange, or similar appurtenance is welded to a piece of pipe, the resulting assembly becomes a ‘fitting’ and must be individually listed. These types of connections were considered by IAPMO to be different than a ‘welded joint’ which is prescriptively allowed per Section 605.13.2.
There is at least one local fabrication shop that has gone through the steps of obtaining the appropriate IAPMO and NSF listings for these types of fabricated assemblies. If your firm is interested in doing the same, you will need to reach out directly to NSF and IAPMO to inquire about the current process, including projected timelines and associated costs. You will need to submit a list of the fitting types you wish to have certified and send in samples to be lab tested. When applying for NSF 61 certification, you will need to indicate if the fittings are intended to be used for cold water only, or for both cold and hot water (Commercial – 180° or Domestic – 140°). Certification will most likely include a visit of your manufacturing facility and ongoing annual recertification. Obtaining IAPMO PS 53 certification is a similar but separate process from NSF 61 certification.
When all of your fabricated assemblies have been tested and certified, you will receive authorization from both NSF and IAPMO to apply the NSF and IAPMO (UPC) symbols to your products (stickers or etchings). These are the markings our field inspectors will expect to see prior to signing off on a potable domestic water distribution system using these types of fittings. These listings will be periodically checked against the online IAPMO and NSF product listing websites to confirm the listing is active and appropriate to the use of the fitting.
Please note, the fitting listing requirement has been part of the UPC for many code cycles for all allowable materials within domestic water systems. Public Health’s current enforcement policy regarding fabricated stainless steel fittings and assemblies is not directly related to any specific code cycle or the adoption of future editions of the Plumbing Code. This enforcement policy has been in place for well over a year as a matter of ensuring public health. We are making a concerted effort to convey this information consistently and repeatedly to counteract rumors and misunderstanding surrounding this issue. If you have any remaining questions, please feel free to reach out via email to: planreviewinfo@kingcounty.gov and we will do our best to provide a thorough and personalized response.
|